Circuit Protection · Selection Guide
A practical NZM selection workflow for panel builders: frame size first, then protection ratings, installation details and frame-compatible accessories.
The NZM family covers compact moulded-case circuit breakers for distribution and motor-related protection. Frame size is a useful first filter, but the exact breaker still needs to match the electrical duty, fault level, trip function and panel installation.
Quick answer: Use frame size to narrow the family, not as a substitute for checking the exact current and interrupting rating.

At a glance
In this guide
Frame size is a mechanical and electrical boundary: it affects the current range, dimensions, connection options and the accessories that can be fitted. Eaton describes the NZM portfolio as a four-frame family with ratings across the overall range of approximately 20 A to 1,600 A; the frame limits below are more useful as an initial filter than as a final part-number selection.
| NZM frame | Current capacity shown in Eaton catalogue | Typical use described in source draft | Selection reminder |
|---|---|---|---|
| Frame 1 | Up to 160 A | Distribution feeders; smaller motors | Check exact breaker rating, trip unit and interrupting capacity. |
| Frame 2 | Up to 300 A | Main incomers; larger motors | Confirm busbar, terminal and enclosure clearances. |
| Frame 3 | Up to 630 A | Transformer feeders; heavy motor starting | Review coordination and inrush/starting conditions. |
| Frame 4 | Up to 1,600 A | Main incomers; high-capacity distribution | Confirm panel dimensions, connections and protection settings. |
Important catalogue check
The source draft listed narrower ranges (20–125 A, 70–250 A, 250–630 A and 600–1,250 A). Eaton’s current public NZM catalogue lists the frame ceilings as 160 A, 300 A, 630 A and 1,600 A. These figures are not necessarily a one-to-one comparison of every regional or legacy variant, so confirm the exact model family and catalogue edition before publishing a part-level claim.
Do not select the frame by rated current alone. The final breaker must also satisfy the installation voltage, available fault current, required interrupting capacity, protection function, pole count, connection arrangement and applicable approvals. Frame dimensions and mounting details should be settled before the panel layout is frozen.
The source draft correctly highlights frame-specific accessories. Treat the breaker and its accessories as a single bill of materials rather than buying accessories from a family name alone.
| Accessory | Purpose | What to confirm before ordering |
|---|---|---|
| Hinged front cover / door-coupling parts | Panel-door mounting and operator access | Frame, breaker type, door thickness and shaft/coupler requirements. |
| Rotary handle | Manual operation and door interlocking where supported | Frame, mounting style, shaft length and operating arrangement. |
| Shunt trip release | Remote electrical tripping | Compatible breaker/frame and release control voltage. |
| Undervoltage release | Trips or prevents closing when supply voltage falls, per device design | Release voltage, operating logic and frame compatibility. |
| Auxiliary contacts | Remote status indication to control or monitoring systems | Contact configuration, wiring needs and compatibility. |
The source draft groups “DIL/DILM” under legacy breaker products. That label needs a technical check: Eaton’s DILM product pages identify DILM as a contactor series, while NZM is the moulded-case circuit breaker family. If an existing panel is labelled DIL or DILM, first identify the actual device and function; do not assume it is an NZM breaker or a mechanically interchangeable replacement. Use Eaton’s exact cross-reference and the original panel drawings.
No. Frame size defines a family boundary; the exact rated current, trip unit, interrupting rating and options depend on the selected model.
Do not assume so. Check the accessory part number and compatibility table for the exact frame and breaker variant.
They perform different functions. Identify the installed device and required function before choosing a replacement; use manufacturer cross-reference documentation.
Send the complete NZM catalogue number, voltage, rated current, required trip function, fault level and accessory list. These details are needed to confirm an electrically and mechanically compatible configuration.