NH Fuse Selection Guide: Bussmann NH00 to NH4 for Industrial Power Distribution

Time:2026-10-15   Author:深圳安鸣科技   Browse:

If you've opened a European or Chinese low-voltage distribution panel, you've seen NH fuses. The distinctive rectangular ceramic body, the two blade terminals, the striker pin on top — the NH (Niederspannungs-Hochleistungs) format is the backbone of IEC-style industrial power distribution worldwide.

But NH fuses come in five standard sizes, multiple voltage classes, and several operating categories. Getting the combination right determines whether your panel protects properly or nuisance-trips through production.

This guide covers the complete Bussmann NH range with size charts, selection examples, and the bases you need to mount them.

What Is an NH Fuse?

NH stands for Niederspannungs-Hochleistungs-Sicherung — German for "low-voltage high-breaking-capacity fuse." Standardized under IEC 60269-2, the NH system is defined by fixed physical dimensions that guarantee interchangeability between manufacturers.

That interchangeability is the NH system's superpower: a Bussmann NH1-160A fits any DIN NH1 base, from any panel builder, anywhere in the world.

The NH Size System

Size Body Height Body Width Blade Gap Max Current Typical Application
NH00 78mm 55mm 135mm 160A Small distribution, control panels
NH1 135mm 65mm 135mm 250A Sub-distribution, motor feeders
NH2 150mm 75mm 150mm 400A Main distribution, large feeders
NH3 150mm 95mm 150mm 630A Main incoming, busbar protection
NH4 200mm 115mm 200mm 1250A Main switchboard, transformer LV side

Critical note: NH00 and NH1 share the same 135mm blade gap (NH00 is shorter in height). This is why NH00 fuses can be installed in NH1 bases with adapters — but never the reverse.

Bussmann NH Product Families

Standard NH Series (gG)

The general-purpose gG line for cable and distribution protection:

Model Size Voltage Typical Currents
NH00-40A NH00 500VAC / 690VAC 40A
NH00-63A NH00 500VAC / 690VAC 63A
NH00-80A NH00 500VAC / 690VAC 80A
NH00-100A NH00 500VAC / 690VAC 100A
NH00-125A NH00 500VAC / 690VAC 125A
NH00-160A NH00 500VAC / 690VAC 160A
NH1-125A NH1 500VAC / 690VAC 125A
NH1-160A NH1 500VAC / 690VAC 160A
NH1-200A NH1 500VAC / 690VAC 200A
NH1-250A NH1 500VAC / 690VAC 250A
NH2-250A NH2 500VAC / 690VAC 250A
NH2-315A NH2 500VAC / 690VAC 315A
NH2-400A NH2 500VAC / 690VAC 400A
NH3-500A NH3 500VAC / 690VAC 500A
NH3-630A NH3 500VAC / 690VAC 630A
NH4-630A NH4 500VAC / 690VAC 630A
NH4-800A NH4 500VAC / 690VAC 800A
NH4-1000A NH4 500VAC / 690VAC 1000A
NH4-1250A NH4 500VAC / 690VAC 1250A

NHG Series — Higher Voltage Variants

The NHG designation indicates higher voltage ratings for specialized applications:

Model Size Voltage Notes
NHG-500 NH00–NH3 500VAC Standard industrial AC
NHG-690 NH00–NH3 690VAC Higher voltage industrial

The 690VAC rating matters for installations using 690V distribution (common in heavy industry and data centers).

DC-Capable NH Variants

For DC applications, Bussmann offers NH fuses with explicit DC ratings:

Model Size Voltage Application
PV-63ANH NH00 1000VDC Solar combiner output
PV-200ANH NH1 1000VDC Solar sub-array
BSF-250A NH1 1000VDC Battery storage (gBat)

Do not assume standard NH AC fuses work in DC circuits — verify the DC rating on the datasheet. Most standard NH fuses carry no DC rating at all.

The OperatorClass System

Every NH fuse carries a two-letter operating class marking:

Class Meaning When to Use
gG General purpose, full-range Cable and distribution protection
gL Legacy cable protection (equivalent to gG) Older specifications
aM Motor circuits, partial range Motor short-circuit protection
aR Semiconductor, partial range Rectifier/IGBT protection (high speed)
gBat Battery storage BESS (see BSF series)
gPV Photovoltaic Solar DC (see PV-ANH series)

gG vs aM selection rule: If the load is a cable or transformer, use gG. If the load is a motor, use aM — because gG fuses may nuisance-open on motor starting inrush.

NH Fuse Selection: A Four-Step Method

Step 1: Determine the Load Current

Calculate the maximum continuous current of the circuit being protected. For a distribution feeder, this is the sum of downstream loads × demand factor.

Step 2: Apply the Safety Factor

In (NH fuse) ≥ Iload × Safety Factor
Circuit Type Safety Factor
Cable/feeder 1.1–1.25
Transformer primary 1.5–2.0
Motor (with aM) 1.5–2.0
Capacitor bank 1.35–1.5

Step 3: Check Temperature Derating

NH fuses are rated at 25°C reference ambient. In a hot panel (40–55°C typical for dense switchgear), apply derating:

Ambient Derating Factor NH00-160A Effective
25°C 1.00 160A
35°C 0.95 152A
45°C 0.88 141A
55°C 0.80 128A

Step 4: Verify Selectivity

Check that the downstream NH fuse opens before the upstream one:

I²t (downstream, total) < I²t (upstream, pre-arcing)

Worked Example: 400V Distribution Panel

System: - Main incoming: 630A, 400VAC - Sub-feeder 1: 250A, feeds a motor control center - Sub-feeder 2: 160A, feeds a lighting and socket distribution board

Selection:

Position Load Selected Fuse Reasoning
Main incoming 630A NH3-630A (690VAC) Matches rating, 690V for headroom
Sub-feeder 1 (MCC) 250A NH2-315A 250A × 1.25 = 313A → 315A
Sub-feeder 2 (lighting) 160A NH00-160A Direct rating match, compact
Motor branch (45kW) ~85A FLC NH1-160A aM Motor curve rides through starting

NH Fuse Bases and Accessories

Bussmann provides the complete mounting ecosystem:

Base Model Fuse Sizes Poles Mounting
SD00 NH00 1 DIN rail / panel
SD1 NH1 1 DIN rail / panel
SD2 NH2 1 Panel
SD3-SC NH3 1 Panel, with cover
SD4-SC NH4 1 Panel, with cover
SD-D-PV NH00–NH2 1 PV/DC rated
SD-S-PV NH00–NH2 1 PV/DC rated, compact

Striker pin options: All Bussmann NH fuses can be supplied with a striker pin for remote indication. Pair with a microswitch (e.g., 170H0069) to send a signal to a PLC or SCADA system when the fuse operates.

NH vs. Other Fuse Formats

Format Standard Main Market Size Range
NH IEC 60269-2 Europe, China, global 16A–1250A
BS88 BS 88-2 UK, Commonwealth 2A–1250A
Class J UL 248-8 North America 1A–600A
Class RK5 UL 248-12 North America 0.1A–600A

Circuit duty checklist

Record maximum operating voltage and whether the circuit is AC or DC. Determine continuous load, any motor or transformer inrush, conductor ampacity and the prospective short-circuit current at the fuse location. If this is a replacement, obtain the complete link and base part numbers. The original part is a better starting point than a generic NH size table.

Confirm the exact link and base

Eaton catalogs show NH sizes and multiple ratings, but the series and catalog number determine the exact dimensions, voltage, breaking capacity, losses, indicator, and compatible base. Check the base's terminal connection, thermal limit and enclosure. A larger physical size is not automatically required by every higher load, and two links of one NH size may have different duties.

For a replacement, compare the old and new catalog numbers, utilization category, rated current, AC/DC voltage, interrupt rating and mounting dimensions. For a new installation, check time-current coordination with the upstream and downstream protective devices, and use qualified personnel for isolation and service.

Common NH selection mistakes

· Reading NH00, NH1 or NH3 as a fixed ampere rating rather than a frame size.

· Treating 500 V AC and 690 V AC variants as identical because the link fits.

· Choosing an aM or aR link for conductor overload protection without a complete protection scheme.

· Treating a visual indicator as proof that the circuit is isolated and safe to touch.

Sources for verification

Eaton low voltage catalog  •  Eaton Fuseology


Common Questions

Q: Can I use a 500V NH fuse in a 690V system? A: No. The fuse voltage rating must meet or exceed the system voltage. Using a 500V fuse at 690V risks failure to interrupt a fault. Always select NHG-690 for 690V systems.

Q: Is an NH00 fuse interchangeable with an NH1? A: Physically, an NH00 fits an NH1 base (same 135mm blade gap), but an NH1 will NOT fit an NH00 base. Always confirm the base's designed fuse size with the panel builder.

Q: Do NH fuses come with indicators? A: Yes — Bussmann NH fuses are available with striker pins for visual and remote indication. Specify the indicator option when ordering.

Q: What's the breaking capacity of a Bussmann NH fuse? A: Standard Bussmann NH fuses deliver 120kA at 500VAC and 50–100kA at 690VAC, depending on size. Check the specific datasheet for the exact value at your voltage.