New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
Our recent High-Voltage DC Fuse Selection Decision Tree laid out the voltage-tier logic for specifying Bussmann high-speed fuses across 500 V to 1500 Vdc. The most common follow-up question we received:
This guide is the answer. We walk through a standard 5 MWh / 2.5 MW containerized BESS — the most common configuration in the 2024–2026 utility-scale and C&I storage market — and give you the complete Bill of Materials (BOM) with the Bussmann part number specified at every protection point. By the end you will have a single reference for the entire protection architecture of a 1000 Vdc BESS container, with clear logic for why each Bussmann family was selected.
This article is the second in a two-part series. Read the fuse selection logic first: High-Voltage DC Fuse Selection Decision Tree: 500 V to 1500 V.
A standard 5 MWh / 2.5 MW BESS container is built around a 1000 Vdc battery bus, with battery racks arranged in 2–4 strings feeding a central 2.5 MW Power Conversion System (PCS), then stepped up to 10–35 kVac for grid connection. The reference design we are specifying is based on a 20-foot high-cube ISO container (6.06 × 2.44 × 2.90 m) with 18 battery racks of 280 kWh each, liquid-cooled LFP cells.
Item | Value |
Total energy | 5.04 MWh (18 × 280 kWh) |
AC power rating | 2.5 MW (2 × 1.25 MW PCS in parallel) |
Battery chemistry | LFP, 280 Ah cells, 1P52S per pack |
DC bus voltage | 1000 Vdc nominal (800–1150 Vdc operating range) |
AC grid connection | 10 kVac or 35 kVac (medium voltage) |
Container | 20 ft HC ISO, IP55, C4 corrosion |
Cooling | Liquid cooling, 2× 40 kW HVAC units |
Fire suppression | Perfluorinated ketone (FK-5-1-12) + deflagration vent |
Target standards | UL 9540A, IEC 62619, GB/T 36276, NFPA 855 |
Grid (10/35 kVac)
└── MV transformer (2.5 MVA, Dyn11)
└── MV switchgear with VCB + protection relay
└── LV AC bus (400 Vac 3-ph)
├── PCS #1 (1.25 MW) ──┐
└── PCS #2 (1.25 MW) ──┤
DC bus (1000 Vdc)
├── Battery string 1 (6 racks × 280 kWh)
├── Battery string 2 (6 racks × 280 kWh)
└── Battery string 3 (6 racks × 280 kWh)
└── Auxiliary distribution (400/230 Vac)
├── HVAC #1, #2 | Fire suppression panel
├── Lighting, outlets | EMS, BMS, comms rack
└── Surge protection (AC + DC + signal)
The 5 MWh container is essentially three independent subsystems running in parallel: the high-voltage DC power path (battery ↔ PCS), the medium-voltage AC grid path (PCS ↔ grid), and the auxiliary system path (HVAC, fire, controls, comms). Each subsystem has its own protection philosophy and its own Bussmann family.
The battery system is the heart of the container — 18 racks of LFP modules, organized into three strings of 6 racks each. Each rack operates at 1000 Vdc nominal with a string current of approximately 1500 A at the DC bus.
Item | Specification | Bussmann Part |
Battery module | 52S 280Ah LFP, 52.6 kWh per pack | — |
Modules per rack | 8 packs in series (416S total → 1000 Vdc) | — |
Rack-level BMS | Master BMS with cell monitoring | — |
Rack DC disconnect | 1500 V / 630 A DC contactor | Bussmann 170Hxxxx contactor base |
Rack DC fuse | 170M18XX series, 1000 Vdc / 50 kA / tc=1 ms, 500 A | 170M1850D or 170M5850D (Size 2) |
Rack pre-charge | NTC thermistor + bypass contactor | — |
String current sensor | 1500 A Hall-effect | — |
Why 170M18XX and not 170M17XX: at 1000 Vdc nominal with operating transients reaching 1150 Vdc, the 17XX family's 800 Vdc rating is insufficient. The 18XX family provides the full 1000 Vdc rating with the same square-body form factor and DIN 43653 mounting. Selection rule from our decision tree: 1000 Vdc → 170M18XX.
Why 500 A and not higher: each rack contributes 6 × 280 Ah / 6 in parallel = 280 Ah at the string level, with a 1.5× derating margin for the rack fuse (1400 A string ÷ 18 racks = ~78 A per rack, but the rack fuse protects the rack-internal short circuit, not the string current — the proper sizing is per the I²t of the rack's contribution to a string short circuit, which falls in the 400–630 A range for a 52S LFP rack at 1000 Vdc). 500 A is the industry-consensus point.
Item | Specification | Bussmann Part |
String-level contactor | 1500 V / 1500 A DC contactor with mechanical interlock | Eaton DILM series contactor |
String main fuse | 170M18XX 1000 Vdc, 800 A | 170M1880D (Size 2 or 3) |
String pre-charge | 50 Ω NTC + bypass | — |
String current sensor | 2000 A Hall-effect | — |
String ground fault detector | Residual current monitoring | Bender IR155 |
Item | Specification | Bussmann Part |
DC main disconnect | 1500 V / 2000 A load break switch | Bussmann 170Hxxxx disconnect base |
DC main fuse | 170M18XX 1000 Vdc, 1250 A | 170M5813D (Size 3) |
DC surge protection | Type 2 SPD, 1000 Vdc, 40 kA | Eaton SPD for PV/DC applications |
DC grounding | Mid-point grounding kit | — |
Insulation monitor | IEC 61557-8 compliant | Bender ISOMETER |
The PCS is the bidirectional inverter that connects the 1000 Vdc battery bus to the 400 Vac LV bus. For a 5 MWh container, the typical configuration is two parallel 1.25 MW units for redundancy and partial-load efficiency.
Item | Specification | Bussmann Part |
DC link capacitor pre-charge | NTC thermistor + bypass contactor | — |
DC-side fast fuse | 170M18XX 1000 Vdc, 500 A (×3 per PCS for 3-level NPC topology) | 170M1850D |
IGBT module | 1700 V / 1000 A IGBT, water-cooled | — |
AC-side fast fuse | 170M17XX 800 Vdc, 800 A (per phase, 3×) | 170M1780D |
AC EMI filter | Common-mode + differential-mode choke | — |
LCL filter | Three-phase LCL, 1500 A | — |
Control board | DSP + FPGA, fiber comms to BMS | — |
Why 170M17XX on the AC side even at 800 Vdc rating: the AC-side fuse is a back-up protection for the IGBT module. The IGBT's collector-emitter voltage rating is 1700 V, and the AC bus peak voltage is 400 × √2 = 565 V — well within the 170M17XX 800 Vdc rating. Using 170M18XX here is over-spec and cost-inefficient.
Item | Specification | Bussmann Part |
AC circuit breaker | 400 Vac / 2500 A, 65 kA | Eaton NZM3 or equivalent |
AC surge protection | Type 1+2 SPD, 400 Vac, 25 kA | Eaton SPD for 400 Vac |
Disconnect switch | 400 Vac / 2500 A | — |
For grid connection, the 400 Vac LV bus is stepped up to 10 kVac (typical for small-to-medium BESS plants) or 35 kVac (for large utility plants).
Item | Specification | Bussmann Part |
Transformer | 2.5 MVA, 10(±2×2.5%)/0.4 kV, Dyn11, ONAN | — |
Oil temperature sensor | Pt100 + Buchholz relay | — |
Pressure relief valve | With signal contact | — |
Bayonet fuse (HV side) | 170M58XX series or DIN HV HRC fuse 10 kV, 200 A | 170M5820D or equivalent |
Protection relay | Differential + overcurrent + REF | SEL-751 or equivalent |
Item | Specification | Bussmann Part |
Vacuum circuit breaker | 12 kV / 1250 A / 25 kA | Eaton VCP-W or equivalent |
Current transformer | 1200/5 A, 5P20 | — |
Voltage transformer | 10000/√3 : 100/√3 | — |
Surge arrester | 12 kV metal-oxide, 10 kA | — |
Why 170M58XX on the HV side: the MV transformer is protected by a dedicated bayonet fuse sized for the transformer inrush current (typically 8–12× rated for 0.1 s). The 170M58XX family provides the high I²t withstanding needed for transformer energization while still offering fast enough operation for internal HV faults. For BESS applications with frequent charge/discharge cycles, the high cycle count of the 58XX series (vs. NH-style fuses) is a secondary benefit.
Item | Specification | Bussmann Part |
Main LV circuit breaker | 400 Vac / 2500 A / 65 kA, draw-out | Eaton IZMX40 or equivalent |
PCS branch breakers | 400 Vac / 1600 A / 65 kA (×2) | Eaton NZM4 or equivalent |
HVAC branch breaker | 400 Vac / 100 A, MCB | Eaton PLS6-C100 |
Fire panel supply | 230 Vac / 16 A, MCB | Eaton PLS6-C16 |
Lighting + outlets | 230 Vac / 16 A, MCB | Eaton PLS6-C16 |
EMS/BMS supply (UPS-backed) | 230 Vac / 10 A, MCB + UPS | Eaton 5PX 1500 VA |
AC SPD upstream | Type 1+2, 400 Vac, 25 kA | Eaton SPD for 400 Vac |
Why RT16 / NH1 gG on the AC side: as discussed in our Depot Infrastructure Protection Guide, the RT16 / NT00 / NH1 gG series is the European/IEC standard for AC distribution protection. gG (general-purpose, full-range breaking) covers both overload and short-circuit, making it the right choice for fixed loads like HVAC and lighting.
The auxiliary systems keep the battery at optimal temperature and contain any thermal event. They are protection-critical, not just comfort.
Item | Specification | Bussmann Part |
Liquid cooling unit | 40 kW, 7 °C outlet, -30 to +55 °C ambient | — |
Circulation pump | 1.5 kW, 400 Vac 3-ph | — |
Coolant | 50/50 ethylene glycol-water | — |
Compressor fuse | 400 Vac / 25 A, aM class | Bussmann 170M26XX or NH00 aM |
Pump fuse | 400 Vac / 6 A, gG class | NH00 gG 6A |
Temperature sensor | Pt100, BMS-monitored | — |
Condensate drain | Heated, IP67 | — |
Why aM on the compressor and gG on the pump: compressor loads have very high locked-rotor current (5–7× full load) that would nuisance-trip a gG fuse during startup. aM (motor protection) class fuses have a higher inrush tolerance while still protecting against short circuits.
Item | Specification | Bussmann Part |
Detection | Aspirating smoke detection (VESDA) + off-gas sensor (H2, CO) | — |
Suppression agent | FK-5-1-12 (3M Novec 1230), 200 kg per container | — |
Agent bottle heater | 230 Vac / 100 W, self-regulating | — |
Control panel | UL 864 / EN 54 compliant, addressable | — |
Deflagration vent | Top-mounted, 4 m², certified to NFPA 68 | — |
Control panel fuse | 24 Vdc / 3 A, gG | FWA-3A or 170M series |
Battery heater fuse | 230 Vac / 4 A, gG | NH00 gG 4A |
The energy management system (EMS), battery management system (BMS), and communication network are the brain of the container. They are also the subsystem most often built with consumer-grade components that fail in the field — particularly the physical connectors.
Item | Specification | Bussmann / Connector Part |
EMS controller | Industrial PC, fanless, IEC 61850-3 | — |
BMS master | Distributed, fiber-optic link to rack BMS | — |
Local SCADA | Touch panel HMI, 15" outdoor-readable | — |
Ethernet switch | Managed, 8-port, DIN-rail, -40 to +75 °C | — |
Cellular modem | 4G/5G industrial gateway, dual-SIM | — |
Time sync | GPS + PTP grandmaster | — |
Diagnostic / firmware-update port | Industrial USB Type-C, locking, IP67 | GSCONN industrial USB-C |
EMS-to-BMS fiber port | Industrial LC duplex, IP67 | Industrial fiber connector |
Cell-tower / wireless port | N-type, IP67 | N-type coax connector |
Field service port (RJ45) | Industrial RJ45 jack, IP67, locking | Industrial RJ45 |
The connector point is critical. In a 5 MWh container operating at 10–55 °C ambient with daily thermal cycling, vibration from HVAC, and 24/7 uptime, consumer-grade USB or RJ45 jacks will fail within 12–18 months. Industrial-grade locking connectors with IP67 sealing and -40 to +85 °C temperature range are the only reliable choice.
GSCONN supplies industrial-grade locking USB Type-A, Type-C, and stacked-port configurations designed for EV charging and BESS cabinet environments — the same physical interfaces built to the same field demands as the Bussmann protection package.
Item | Specification |
Container size | 20 ft HC ISO (6.06 × 2.44 × 2.90 m) |
IP rating | IP55 (rain + dust) |
Corrosion class | C4 (industrial/coastal) |
Thermal insulation | 50 mm PIR, R = 2.2 m²K/W |
Cable entry | Bottom-entry gland plates, IP67 |
Door access | 4 personnel doors, 1 equipment door (racks side) |
Door interlock | Mechanical + electrical, with main disconnect interlock |
Internal lighting | LED, 5000 K, 100 lux at floor |
Grounding | 2× M10 ground bosses, Cu bus bar |
Lifting | 4 ISO corner castings + forklift slots |
Subsystem | Location | Bussmann Part | Qty/Container | Reference |
Battery | Rack-level DC fuse | 170M1850D (1000 Vdc, 500 A) | 18 | Tier 4 |
Battery | String main fuse | 170M1880D (1000 Vdc, 800 A) | 3 | Tier 4 |
Battery | HV-Box main fuse | 170M5813D (1000 Vdc, 1250 A) | 1 | Tier 4 |
PCS | DC-side fast fuse | 170M1850D (×3 per PCS) | 6 | Tier 4 |
PCS | AC-side fast fuse | 170M1780D (800 Vdc, 800 A) | 6 | Tier 3 |
MV | Transformer bayonet | 170M5820D (or DIN HV HRC) | 3 | Tier 5 |
LV | Main LV breaker | Eaton IZMX40 (or equivalent) | 1 | Section 5 |
LV | AC SPD upstream | Eaton SPD 400 Vac | 1 | Section 5 |
DC | DC SPD upstream | Eaton SPD 1000 Vdc | 1 | Section 2.3 |
HVAC | Compressor fuse | 170M26XX / NH00 aM | 2 | Section 6.1 |
HVAC | Pump fuse | NH00 gG 6A | 2 | Section 6.1 |
Fire | Control panel fuse | FWA-3A | 1 | Section 6.2 |
Fire | Battery heater fuse | NH00 gG 4A | 1 | Section 6.2 |
Aux | UPS supply | Eaton 5PX 1500 VA | 1 | Section 5 |
Aux | Lighting + outlets | Eaton PLS6-C16 | 6 | Section 5 |
Aux | HVAC supply | Eaton PLS6-C100 | 2 | Section 5 |
Total Bussmann part count: approximately 50–55 protection devices per 5 MWh container, excluding the medium-voltage switchgear (which is a separate Eaton product line).
Use this checklist when reviewing or specifying a 5 MWh containerized BESS:
[ ] DC bus voltage confirmed at 1000 Vdc nominal, with full operating range (typically 800–1150 Vdc)
[ ] Rack-level fuse sized at 500 A with 170M18XX (1000 Vdc / 50 kA / tc=1 ms)
[ ] String main fuse sized at 800 A with 170M18XX
[ ] HV-Box main fuse sized at 1250 A with 170M5813D (Size 3) — verify thermal coordination with disconnect switch
[ ] PCS DC fuses matched to IGBT module I²t (verify with PCS vendor's coordination curve)
[ ] PCS AC fuses sized for 800 Vdc / 800 A (170M17XX) — back-up only
[ ] MV transformer bayonet fuse coordinated with inrush and secondary LV breaker let-through
[ ] AC SPD upstream of PCS (Type 1+2, 25 kA, 400 Vac)
[ ] DC SPD at HV-Box input (Type 2, 40 kA, 1000 Vdc)
[ ] HVAC compressor fuses are aM class (not gG)
[ ] Fire suppression has dedicated branch circuit, not shared with HVAC
[ ] Industrial connectors specified for all external ports (USB, RJ45, fiber, coax) — no consumer-grade
[ ] IP rating of enclosure confirmed at IP55 minimum; cable entries IP67
[ ] Standards compliance verified: UL 9540A, IEC 62619, GB/T 36276, NFPA 855
[ ] Thermal management verified: HVAC capacity (40 kW liquid cooling per string), BMS thermal sensors per cell
[ ] Ground fault detection at the string level (Bender IR155 or equivalent)
[ ] Insulation monitoring at the DC bus (Bender ISOMETER or equivalent)
[ ] Door interlocks mechanically interlocked with main disconnect, electrically interlocked with PCS
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.