In need of urgent assistance? Call +86-13427815151 

新闻与咨询

New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc. 

5 MWh Containerized BESS Complete BOM: 1000 Vdc Architecture with Full Bussmann Protection

Time:2026-06-25   Author:As Beam   Browse:

From Decision Tree to a Real System

Our recent High-Voltage DC Fuse Selection Decision Tree laid out the voltage-tier logic for specifying Bussmann high-speed fuses across 500 V to 1500 Vdc. The most common follow-up question we received:

This guide is the answer. We walk through a standard 5 MWh / 2.5 MW containerized BESS — the most common configuration in the 2024–2026 utility-scale and C&I storage market — and give you the complete Bill of Materials (BOM) with the Bussmann part number specified at every protection point. By the end you will have a single reference for the entire protection architecture of a 1000 Vdc BESS container, with clear logic for why each Bussmann family was selected.

This article is the second in a two-part series. Read the fuse selection logic first: High-Voltage DC Fuse Selection Decision Tree: 500 V to 1500 V.

bess.jpg 

1. System Architecture Overview

A standard 5 MWh / 2.5 MW BESS container is built around a 1000 Vdc battery bus, with battery racks arranged in 2–4 strings feeding a central 2.5 MW Power Conversion System (PCS), then stepped up to 10–35 kVac for grid connection. The reference design we are specifying is based on a 20-foot high-cube ISO container (6.06 × 2.44 × 2.90 m) with 18 battery racks of 280 kWh each, liquid-cooled LFP cells.

Reference Design Specification

Item

Value

Total energy

5.04 MWh (18 × 280 kWh)

AC power rating

2.5 MW (2 × 1.25 MW PCS in parallel)

Battery chemistry

LFP, 280 Ah cells, 1P52S per pack

DC bus voltage

1000 Vdc nominal (800–1150 Vdc operating range)

AC grid connection

10 kVac or 35 kVac (medium voltage)

Container

20 ft HC ISO, IP55, C4 corrosion

Cooling

Liquid cooling, 2× 40 kW HVAC units

Fire suppression

Perfluorinated ketone (FK-5-1-12) + deflagration vent

Target standards

UL 9540A, IEC 62619, GB/T 36276, NFPA 855

Main Single-Line Topology

Grid (10/35 kVac)

  └── MV transformer (2.5 MVA, Dyn11)

       └── MV switchgear with VCB + protection relay

            └── LV AC bus (400 Vac 3-ph)

                 ├── PCS #1 (1.25 MW) ──┐

                 └── PCS #2 (1.25 MW) ──┤

                                       DC bus (1000 Vdc)

                                       ├── Battery string 1 (6 racks × 280 kWh)

                                       ├── Battery string 2 (6 racks × 280 kWh)

                                       └── Battery string 3 (6 racks × 280 kWh)

            └── Auxiliary distribution (400/230 Vac)

                 ├── HVAC #1, #2  |  Fire suppression panel

                 ├── Lighting, outlets  |  EMS, BMS, comms rack

            └── Surge protection (AC + DC + signal)

The 5 MWh container is essentially three independent subsystems running in parallel: the high-voltage DC power path (battery ↔ PCS), the medium-voltage AC grid path (PCS ↔ grid), and the auxiliary system path (HVAC, fire, controls, comms). Each subsystem has its own protection philosophy and its own Bussmann family.

 

2. High-Voltage Battery System BOM

The battery system is the heart of the container — 18 racks of LFP modules, organized into three strings of 6 racks each. Each rack operates at 1000 Vdc nominal with a string current of approximately 1500 A at the DC bus.

2.1 Battery Rack (×18, identical)

Item

Specification

Bussmann Part

Battery module

52S 280Ah LFP, 52.6 kWh per pack

Modules per rack

8 packs in series (416S total → 1000 Vdc)

Rack-level BMS

Master BMS with cell monitoring

Rack DC disconnect

1500 V / 630 A DC contactor

Bussmann 170Hxxxx contactor base

Rack DC fuse

170M18XX series, 1000 Vdc / 50 kA / tc=1 ms, 500 A

170M1850D or 170M5850D (Size 2)

Rack pre-charge

NTC thermistor + bypass contactor

String current sensor

1500 A Hall-effect

Why 170M18XX and not 170M17XX: at 1000 Vdc nominal with operating transients reaching 1150 Vdc, the 17XX family's 800 Vdc rating is insufficient. The 18XX family provides the full 1000 Vdc rating with the same square-body form factor and DIN 43653 mounting. Selection rule from our decision tree: 1000 Vdc → 170M18XX.

Why 500 A and not higher: each rack contributes 6 × 280 Ah / 6 in parallel = 280 Ah at the string level, with a 1.5× derating margin for the rack fuse (1400 A string ÷ 18 racks = ~78 A per rack, but the rack fuse protects the rack-internal short circuit, not the string current — the proper sizing is per the I²t of the rack's contribution to a string short circuit, which falls in the 400–630 A range for a 52S LFP rack at 1000 Vdc). 500 A is the industry-consensus point.

2.2 Battery String Combiner (×3)

Item

Specification

Bussmann Part

String-level contactor

1500 V / 1500 A DC contactor with mechanical interlock

Eaton DILM series contactor

String main fuse

170M18XX 1000 Vdc, 800 A

170M1880D (Size 2 or 3)

String pre-charge

50 Ω NTC + bypass

String current sensor

2000 A Hall-effect

String ground fault detector

Residual current monitoring

Bender IR155

2.3 High-Voltage Box (HV-Box) — 1 per container

Item

Specification

Bussmann Part

DC main disconnect

1500 V / 2000 A load break switch

Bussmann 170Hxxxx disconnect base

DC main fuse

170M18XX 1000 Vdc, 1250 A

170M5813D (Size 3)

DC surge protection

Type 2 SPD, 1000 Vdc, 40 kA

Eaton SPD for PV/DC applications

DC grounding

Mid-point grounding kit

Insulation monitor

IEC 61557-8 compliant

Bender ISOMETER

 

3. Power Conversion System (PCS) BOM

The PCS is the bidirectional inverter that connects the 1000 Vdc battery bus to the 400 Vac LV bus. For a 5 MWh container, the typical configuration is two parallel 1.25 MW units for redundancy and partial-load efficiency.

3.1 PCS Internal Protection (×2)

Item

Specification

Bussmann Part

DC link capacitor pre-charge

NTC thermistor + bypass contactor

DC-side fast fuse

170M18XX 1000 Vdc, 500 A (×3 per PCS for 3-level NPC topology)

170M1850D

IGBT module

1700 V / 1000 A IGBT, water-cooled

AC-side fast fuse

170M17XX 800 Vdc, 800 A (per phase, 3×)

170M1780D

AC EMI filter

Common-mode + differential-mode choke

LCL filter

Three-phase LCL, 1500 A

Control board

DSP + FPGA, fiber comms to BMS

Why 170M17XX on the AC side even at 800 Vdc rating: the AC-side fuse is a back-up protection for the IGBT module. The IGBT's collector-emitter voltage rating is 1700 V, and the AC bus peak voltage is 400 × √2 = 565 V — well within the 170M17XX 800 Vdc rating. Using 170M18XX here is over-spec and cost-inefficient.

3.2 PCS Output to LV Bus

Item

Specification

Bussmann Part

AC circuit breaker

400 Vac / 2500 A, 65 kA

Eaton NZM3 or equivalent

AC surge protection

Type 1+2 SPD, 400 Vac, 25 kA

Eaton SPD for 400 Vac

Disconnect switch

400 Vac / 2500 A

 

4. MV Transformer and Switchgear BOM

For grid connection, the 400 Vac LV bus is stepped up to 10 kVac (typical for small-to-medium BESS plants) or 35 kVac (for large utility plants).

4.1 MV Transformer

Item

Specification

Bussmann Part

Transformer

2.5 MVA, 10(±2×2.5%)/0.4 kV, Dyn11, ONAN

Oil temperature sensor

Pt100 + Buchholz relay

Pressure relief valve

With signal contact

Bayonet fuse (HV side)

170M58XX series or DIN HV HRC fuse 10 kV, 200 A

170M5820D or equivalent

Protection relay

Differential + overcurrent + REF

SEL-751 or equivalent

4.2 MV Switchgear

Item

Specification

Bussmann Part

Vacuum circuit breaker

12 kV / 1250 A / 25 kA

Eaton VCP-W or equivalent

Current transformer

1200/5 A, 5P20

Voltage transformer

10000/√3 : 100/√3

Surge arrester

12 kV metal-oxide, 10 kA

Why 170M58XX on the HV side: the MV transformer is protected by a dedicated bayonet fuse sized for the transformer inrush current (typically 8–12× rated for 0.1 s). The 170M58XX family provides the high I²t withstanding needed for transformer energization while still offering fast enough operation for internal HV faults. For BESS applications with frequent charge/discharge cycles, the high cycle count of the 58XX series (vs. NH-style fuses) is a secondary benefit.

 

5. LV AC Distribution BOM

Item

Specification

Bussmann Part

Main LV circuit breaker

400 Vac / 2500 A / 65 kA, draw-out

Eaton IZMX40 or equivalent

PCS branch breakers

400 Vac / 1600 A / 65 kA (×2)

Eaton NZM4 or equivalent

HVAC branch breaker

400 Vac / 100 A, MCB

Eaton PLS6-C100

Fire panel supply

230 Vac / 16 A, MCB

Eaton PLS6-C16

Lighting + outlets

230 Vac / 16 A, MCB

Eaton PLS6-C16

EMS/BMS supply (UPS-backed)

230 Vac / 10 A, MCB + UPS

Eaton 5PX 1500 VA

AC SPD upstream

Type 1+2, 400 Vac, 25 kA

Eaton SPD for 400 Vac

Why RT16 / NH1 gG on the AC side: as discussed in our Depot Infrastructure Protection Guide, the RT16 / NT00 / NH1 gG series is the European/IEC standard for AC distribution protection. gG (general-purpose, full-range breaking) covers both overload and short-circuit, making it the right choice for fixed loads like HVAC and lighting.

 

6. HVAC and Fire Suppression BOM

The auxiliary systems keep the battery at optimal temperature and contain any thermal event. They are protection-critical, not just comfort.

6.1 HVAC (Liquid Cooling)

Item

Specification

Bussmann Part

Liquid cooling unit

40 kW, 7 °C outlet, -30 to +55 °C ambient

Circulation pump

1.5 kW, 400 Vac 3-ph

Coolant

50/50 ethylene glycol-water

Compressor fuse

400 Vac / 25 A, aM class

Bussmann 170M26XX or NH00 aM

Pump fuse

400 Vac / 6 A, gG class

NH00 gG 6A

Temperature sensor

Pt100, BMS-monitored

Condensate drain

Heated, IP67

Why aM on the compressor and gG on the pump: compressor loads have very high locked-rotor current (5–7× full load) that would nuisance-trip a gG fuse during startup. aM (motor protection) class fuses have a higher inrush tolerance while still protecting against short circuits.

6.2 Fire Suppression

Item

Specification

Bussmann Part

Detection

Aspirating smoke detection (VESDA) + off-gas sensor (H2, CO)

Suppression agent

FK-5-1-12 (3M Novec 1230), 200 kg per container

Agent bottle heater

230 Vac / 100 W, self-regulating

Control panel

UL 864 / EN 54 compliant, addressable

Deflagration vent

Top-mounted, 4 m², certified to NFPA 68

Control panel fuse

24 Vdc / 3 A, gG

FWA-3A or 170M series

Battery heater fuse

230 Vac / 4 A, gG

NH00 gG 4A

 

7. EMS, BMS, and Communications BOM

The energy management system (EMS), battery management system (BMS), and communication network are the brain of the container. They are also the subsystem most often built with consumer-grade components that fail in the field — particularly the physical connectors.

Item

Specification

Bussmann / Connector Part

EMS controller

Industrial PC, fanless, IEC 61850-3

BMS master

Distributed, fiber-optic link to rack BMS

Local SCADA

Touch panel HMI, 15" outdoor-readable

Ethernet switch

Managed, 8-port, DIN-rail, -40 to +75 °C

Cellular modem

4G/5G industrial gateway, dual-SIM

Time sync

GPS + PTP grandmaster

Diagnostic / firmware-update port

Industrial USB Type-C, locking, IP67

GSCONN industrial USB-C

EMS-to-BMS fiber port

Industrial LC duplex, IP67

Industrial fiber connector

Cell-tower / wireless port

N-type, IP67

N-type coax connector

Field service port (RJ45)

Industrial RJ45 jack, IP67, locking

Industrial RJ45

The connector point is critical. In a 5 MWh container operating at 10–55 °C ambient with daily thermal cycling, vibration from HVAC, and 24/7 uptime, consumer-grade USB or RJ45 jacks will fail within 12–18 months. Industrial-grade locking connectors with IP67 sealing and -40 to +85 °C temperature range are the only reliable choice.

GSCONN supplies industrial-grade locking USB Type-A, Type-C, and stacked-port configurations designed for EV charging and BESS cabinet environments — the same physical interfaces built to the same field demands as the Bussmann protection package.

 

8. Container Enclosure BOM

Item

Specification

Container size

20 ft HC ISO (6.06 × 2.44 × 2.90 m)

IP rating

IP55 (rain + dust)

Corrosion class

C4 (industrial/coastal)

Thermal insulation

50 mm PIR, R = 2.2 m²K/W

Cable entry

Bottom-entry gland plates, IP67

Door access

4 personnel doors, 1 equipment door (racks side)

Door interlock

Mechanical + electrical, with main disconnect interlock

Internal lighting

LED, 5000 K, 100 lux at floor

Grounding

2× M10 ground bosses, Cu bus bar

Lifting

4 ISO corner castings + forklift slots

 

9. Complete Bussmann Protection Map (Single-Reference Table)

Subsystem

Location

Bussmann Part

Qty/Container

Reference

Battery

Rack-level DC fuse

170M1850D (1000 Vdc, 500 A)

18

Tier 4

Battery

String main fuse

170M1880D (1000 Vdc, 800 A)

3

Tier 4

Battery

HV-Box main fuse

170M5813D (1000 Vdc, 1250 A)

1

Tier 4

PCS

DC-side fast fuse

170M1850D (×3 per PCS)

6

Tier 4

PCS

AC-side fast fuse

170M1780D (800 Vdc, 800 A)

6

Tier 3

MV

Transformer bayonet

170M5820D (or DIN HV HRC)

3

Tier 5

LV

Main LV breaker

Eaton IZMX40 (or equivalent)

1

Section 5

LV

AC SPD upstream

Eaton SPD 400 Vac

1

Section 5

DC

DC SPD upstream

Eaton SPD 1000 Vdc

1

Section 2.3

HVAC

Compressor fuse

170M26XX / NH00 aM

2

Section 6.1

HVAC

Pump fuse

NH00 gG 6A

2

Section 6.1

Fire

Control panel fuse

FWA-3A

1

Section 6.2

Fire

Battery heater fuse

NH00 gG 4A

1

Section 6.2

Aux

UPS supply

Eaton 5PX 1500 VA

1

Section 5

Aux

Lighting + outlets

Eaton PLS6-C16

6

Section 5

Aux

HVAC supply

Eaton PLS6-C100

2

Section 5

Total Bussmann part count: approximately 50–55 protection devices per 5 MWh container, excluding the medium-voltage switchgear (which is a separate Eaton product line).


10. Selection Checklist (5 MWh Container)

Use this checklist when reviewing or specifying a 5 MWh containerized BESS:

[ ] DC bus voltage confirmed at 1000 Vdc nominal, with full operating range (typically 800–1150 Vdc)

[ ] Rack-level fuse sized at 500 A with 170M18XX (1000 Vdc / 50 kA / tc=1 ms)

[ ] String main fuse sized at 800 A with 170M18XX

[ ] HV-Box main fuse sized at 1250 A with 170M5813D (Size 3) — verify thermal coordination with disconnect switch

[ ] PCS DC fuses matched to IGBT module I²t (verify with PCS vendor's coordination curve)

[ ] PCS AC fuses sized for 800 Vdc / 800 A (170M17XX) — back-up only

[ ] MV transformer bayonet fuse coordinated with inrush and secondary LV breaker let-through

[ ] AC SPD upstream of PCS (Type 1+2, 25 kA, 400 Vac)

[ ] DC SPD at HV-Box input (Type 2, 40 kA, 1000 Vdc)

[ ] HVAC compressor fuses are aM class (not gG)

[ ] Fire suppression has dedicated branch circuit, not shared with HVAC

[ ] Industrial connectors specified for all external ports (USB, RJ45, fiber, coax) — no consumer-grade

[ ] IP rating of enclosure confirmed at IP55 minimum; cable entries IP67

[ ] Standards compliance verified: UL 9540A, IEC 62619, GB/T 36276, NFPA 855

[ ] Thermal management verified: HVAC capacity (40 kW liquid cooling per string), BMS thermal sensors per cell

[ ] Ground fault detection at the string level (Bender IR155 or equivalent)

[ ] Insulation monitoring at the DC bus (Bender ISOMETER or equivalent)

[ ] Door interlocks mechanically interlocked with main disconnect, electrically interlocked with PCS


New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc. 


TAG:   Bussmann Bussmann Fuse 1500VDC DC Fuse ESS Fuse