New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
The contact box — known in North American parlance as the plug-in contact assembly or primary disconnect device — is one of the most dimensionally constrained components in ANSI metal-clad switchgear. It must simultaneously satisfy electrical insulation requirements, current-carrying thermal limits, and physical fit within the current transformer bore. Getting the contact box design wrong means either failing the IEEE C37.20.2 temperature rise test, failing the dielectric withstand test, or being unable to install the current transformers at all.
This article provides a detailed engineering walkthrough of contact box design for ANSI/IEEE C37.20.2 metal-clad switchgear, covering current transformer selection, dimensional envelopes, tulip contact miniaturization, dielectric insulation design, and electric field shielding strategy.

In ANSI metal-clad switchgear, 600V-class through-core (window-type) current transformers are the standard. These CTs are characterized by:
• Power frequency withstand voltage: 3 kV (Vrms)
• Lightning impulse withstand voltage: 10 kV (BIL)
• Secondary current: 5 A (standard North American practice)
• Primary current range: 50 A to 5000/6000 A
This voltage class is appropriate for use at medium-voltage (up to 38 kV) because the CT core sits outside the primary insulation system — the high-voltage primary conductor passes through the window bore, which is occupied by the contact box assembly.
The North American MV CT market is largely standardized around a small number of form factors. Major suppliers include GE ITI (General Electric Instrument Transformers Inc.) and RITZ Instrument Transformers.
The GE ITI Model 780 is the most widely specified current transformer for metal-clad switchgear applications in North America. Its dimensions have become a de facto industry standard, with multiple manufacturers producing dimensionally compatible units.
GE ITI 780 key dimensions:
Parameter | Dimension |
Overall width | 9.8 in (249 mm) |
Window inner diameter | 6.5 in (165 mm) |
Maximum contact box outer diameter | < 160 mm |
This 160 mm outer diameter constraint is the binding dimensional limit for the contact box design. Any contact box with an OD exceeding this value cannot be inserted through the CT bore.
ANSI current transformers for switchgear applications are designed and tested per IEEE C57.13. Key accuracy parameters:
Parameter | Specification |
Metering winding accuracy class | 0.3 (per C57.13) |
Protection winding class | 5P20 |
Secondary current | 5 A |
For small transformation ratios such as 50:5, the standard defines specific accuracy and burden requirements that keep physical CT size within the dimensional envelope needed for contact box installation. Engineers should not over-specify accuracy class or burden rating for small-ratio CTs, as doing so will require a physically larger CT that may not fit within the available window bore.
As established above, the contact box outer diameter is constrained to less than 160 mm by the GE ITI 780 CT window bore. This 160 mm limit applies to the maximum cross-section of the insulated contact body as it passes through the installed CT stack.
For high-current applications, the contact box inner diameter must accommodate the primary draw-out contacts (typically tulip-style or multi-finger contacts). For standard applications, the maximum inner diameter is approximately 140 mm.
This creates a geometric challenge: conventional 3000 A tulip contact assemblies used in IEC-standard switchgear typically have a finger-contact assembly diameter exceeding 140 mm. These cannot be used in ANSI contact box applications without modification.
An additional complication is the difference in temperature rise limits between North American and international standards:
Standard | Maximum Temperature Rise |
IEC (switchgear general) | 75 K above ambient |
IEEE C37.20.2 | 65 K above ambient |
The 10 K stricter limit in IEEE C37.20.2 means that contact resistance and thermal performance requirements for ANSI switchgear contacts are more demanding than equivalent IEC applications. At the same nominal current, less heat can be tolerated — which means the contact interface area must be larger or the material quality must be higher.
Meeting the 3000 A rating within the constraints of an outer diameter below 160 mm and inner diameter below 140 mm requires a purpose-designed miniaturized tulip contact. The key engineering requirements are:
Higher contact pressure reduces the contact resistance (following Holm's contact theory: resistance is inversely related to contact force). For a miniaturized contact assembly where the number of contact fingers is limited by diameter, each individual finger must exert higher spring force to achieve the required total contact pressure.
Material selection for contact springs must balance:
• Spring fatigue life over thousands of connect/disconnect cycles
• Creep resistance at elevated temperature (65 K rise + 40 degrees C ambient = 105 degrees C operating)
• Conductivity to support 3000 A current transfer
In a tulip-style design, current is shared across multiple contact fingers. With a reduced-diameter assembly, fewer fingers can be accommodated around the circumference, each finger must carry proportionally higher current, and conductor cross-section per finger must be increased. A common approach is to use silver-plated copper finger contacts with reinforced cross-sections, combined with precision spring elements to maintain consistent contact force throughout the service life.
Parameter | Standard Tulip Contact | ANSI Miniaturized Design |
Assembly OD | > 140 mm | < 140 mm |
Current rating | 3000 A | 3000 A |
Temperature rise limit | 75 K | 65 K (IEEE C37.20.2) |
Contact pressure | Standard | Increased per finger |
Application | IEC general switchgear | ANSI metal-clad switchgear |
Electric field intensity (E, measured in kV/mm) is the critical parameter in insulation design. For a given voltage, a compact insulation geometry produces a higher electric field intensity than a large-clearance design: E = V / d. At the extreme voltage levels required for 27 kV switchgear (BIL = 125 kV), maintaining adequate insulation margins within a 160 mm OD envelope requires careful material selection and field management.
When two or more insulating media are in series within an electric field, the voltage distribution across each medium is governed by their respective capacitances. A medium with a higher dielectric constant will receive a smaller share of the total voltage because it has larger capacitance, which divides less voltage across itself.
Relevant dielectric constants (relative permittivity):
Material | Dielectric Constant (er) |
Air (dry) | 1.0006 |
Carbon disulfide | ~2.6 |
Epoxy resin | 2.5 - 6.0 |
Water (10 degrees C) | 83.83 |
Key implication: A small air gap in series with a solid epoxy insulator will receive a disproportionately large fraction of the applied voltage because air has a much lower dielectric constant than epoxy. This causes the air gap to be stressed at a field intensity far exceeding its breakdown threshold (~3 kV/mm for air at standard conditions).
The most electrically vulnerable location in any contact box installation is the triple junction point — the microscopic region where the conductor (high voltage), solid insulation (epoxy), and air all meet simultaneously. This geometry is inherent to:
• Contact box installations in the circuit breaker compartment
• Bushing/wall bushing terminations
• Any point where a high-voltage conductor transitions from solid insulation to air
At the triple junction, even a small air gap (< 1 mm) between the contact box outer surface and the adjacent structure can concentrate sufficient voltage to initiate partial discharge or full flashover. For a 27 kV system (test voltage 62 kV AC, BIL 125 kV), this is a critical design concern.
Without shielding, calculation and simulation results show that the air electric field intensity at the triple junction approaches 5 kV/mm for 27 kV systems.
The dielectric withstand strength of air at standard conditions is approximately 3 kV/mm (Paschen curve limit). This means an unshielded 27 kV contact box design will fail voltage withstand testing due to air gap flashover — even if the solid insulation itself is perfectly adequate.
Voltage withstand tests without proper shielding reveal:
• External air gap discharge when only inner shielding is used
• Internal air gap discharge when only outer shielding is used
Both failure modes confirm that the contact box insulation system requires coordinated dual shielding to pass dielectric tests.
The solution to the triple junction problem is the coordinated use of inner shielding (at the conductor-insulation interface) and outer shielding (at the insulation-air interface). When both shields are correctly implemented:
• The electric field is confined entirely within the solid epoxy insulation layer
• No air gap anywhere in the system sees significant voltage stress
• The epoxy layer is exposed to a field intensity of approximately 11.5 kV/mm
For well-formulated epoxy resin (dielectric strength typically > 20 kV/mm in bulk, > 15 kV/mm in molded sections), 11.5 kV/mm is within the reliable long-term operating range.
• Metallic or semiconductive layer applied at the inner surface of the insulation
• Ensures uniform equipotential surface at the conductor boundary
• Eliminates field enhancement at conductor surface irregularities
• Metallic or semiconductive layer applied at the outer surface of the insulation
• Defines the outer equipotential boundary of the insulation system
• Prevents any air-side surface from experiencing voltage stress
When both shields are present and correctly grounded/energized, the full system voltage is applied only across the solid epoxy layer between the two shields — eliminating all air gap stress.
For 27 kV systems (BIL 125 kV), the combination of the 160 mm OD constraint from CT bore, the 140 mm ID constraint from primary contact requirement, 11.5 kV/mm field intensity in epoxy, and the required insulation thickness to achieve BIL 125 kV withstand results in an extremely tight dimensional budget. Achieving all requirements simultaneously requires precision electric field simulation (FEA), careful material qualification, and often multiple design iterations before a configuration passes both power frequency and impulse voltage tests.
Parameter | Value | Constraint Source |
Maximum OD | < 160 mm | GE ITI 780 CT bore |
Maximum ID | < 140 mm | 3000 A contact assembly |
Max temperature rise | 65 K | IEEE C37.20.2 |
CT accuracy class | 0.3 / 5P20 | IEEE C57.13 |
Epoxy field intensity (shielded) | ~11.5 kV/mm | 27 kV BIL 125 kV |
Air field intensity (unshielded) | ~5 kV/mm | 27 kV, small gap |
Air breakdown threshold | ~3 kV/mm | Standard conditions |
Designing a contact box for ANSI/IEEE C37.20.2 metal-clad switchgear requires resolving multiple simultaneous constraints:
• Mechanical fit within the CT window bore (< 160 mm OD for GE ITI 780)
• Electrical contact performance at 3000 A with a 65 K rise limit — requiring miniaturized, high-pressure tulip contacts
• Dielectric integrity through coordinated inner and outer shielding that eliminates air-gap voltage stress
• Dimensional tightness that becomes extremely challenging at 27 kV BIL 125 kV
The contact box sits at the intersection of mechanical engineering, power electronics, and high-voltage physics. Success requires a deep understanding of capacitive voltage distribution, electric field simulation, and current-carrying contact mechanics — all compressed into a cylindrical envelope less than 160 mm in diameter.
Related topics: IEEE C37.20.2 metal-clad switchgear | draw-out circuit breaker design | GE ITI current transformers | RITZ instrument transformers | BIL insulation coordination | partial discharge testing | IEC 62271-200
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.