New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
This article examines the design principles, classification system, pressure relief technologies, and key engineering challenges associated with arc-resistant metal-clad switchgear built to North American standards.

• Low-voltage power distribution switchgear
• Motor control centers (MCCs) at low voltage
• Medium-voltage metal-clad switchgear
• Medium-voltage motor control centers
Type | Accessible Sides | Description |
Type 1 | Front only | Arc-resistant design on front-accessible sides only |
Type 2 | Front, rear, and sides | Arc-resistant design on all freely accessible exterior surfaces |
IEEE C37.20.7 additional requirements:
• Indicator distance from switchgear: 100 mm
• Arc duration: 0.5 seconds
Comparison with IEC: IEC-based standards (e.g., IEC 62271-200) typically require IAC A FLR rating for authorized personnel, with indicators placed at 300 mm from the equipment — a significantly more conservative test setup than the ANSI requirement.
This simulates a realistic operational scenario where maintenance personnel may have the instrument door open while working on relay settings or metering — one of the highest-risk activities in a substation environment. Satisfying Type 2b requirements is considerably more difficult to achieve than standard Type 2, particularly for double-tier circuit breaker lineups.
• The instrument compartment rear channel serves as a shared pressure relief corridor
• Pressure from the lower circuit breaker compartment and bus compartment is routed through this shared channel
• Gas and pressure are then directed through the rear of the upper instrument-only compartment
• Finally, pressure exits through a horizontal top-of-cabinet duct that vents outside the substation building
This architecture efficiently handles multi-compartment pressure relief while minimizing cross-contamination between compartments. The valve flap geometry is optimized to enable rapid depressurization while limiting the blast effect on adjacent compartments.
Key advantage: By routing all pressure through a single shared rear corridor, ABB avoids the need for individual side-mounted pressure relief channels that would compromise structural integrity and thermal ratings in high-fault-current applications.
Patent note: The three-way valve flap system and associated pressure routing architecture are covered by ABB patents. Any alternative design that mimics this routing topology must ensure freedom-to-operate through independent design differentiation.
ABB's switchgear — including the circuit breaker compartment, bus compartment, and cable termination compartment — features dedicated pressure venting paths that direct gas to the cabinet top or designated exit points. This design satisfies the IEEE C37.20.7 requirements for internal arc fault containment and is critical for the Type 2b classification.
• No ventilation holes permitted between compartments
• No cross-compartment pressure pathways are allowed under the Type 2b test
• Each of the six compartments must demonstrate independent venting capability
• The lower-tier breaker compartment, bus compartment, and lower-tier cable compartment must all vent without relying on adjacent spaces
Move the upper auxiliary/instrument compartment forward in the cabinet footprint, freeing rear space behind the lower breaker and bus compartments for dedicated pressure relief ducting. Limitation: Severely constrains primary equipment layout and is incompatible with true double-tier breaker arrangements.
Add bilateral pressure relief channels on each side of the cabinet structure to handle gas venting from lower compartments. Limitation: Channel cross-sectional area is typically insufficient for high fault currents (e.g., 63 kA), and lateral space is rarely available in dense substation layouts.
A pressure absorption chamber connected to multiple or individual compartments, with a mechanism that simultaneously activates dedicated flaps for specific compartments while closing flaps connected to other spaces. This Type 2b-compliant design pattern mirrors the functional intent of the ABB system without duplicating the patented valve geometry.
• Blast protection: Prevent arc-generated plasma and pressure waves from damaging sensitive electronic components during a fault event
• Thermal shielding: Protect relay logic and wiring from radiated heat
Parameter | IEEE C37.20.7 (North America) | IEC 62271-200 (International) |
Indicator distance | 100 mm | 300 mm |
Arc duration | 0.5 s | 0.1 – 1.0 s |
Personnel classification | Not explicitly tiered | A (authorized), B (restricted) |
Type notation | Type 1 / Type 2 / Type 2b | IAC A / IAC B / IAC FL / IAC FLR |
• Selecting an appropriate arc type classification based on application requirements
• Implementing a pressure relief architecture that achieves independent compartment venting without infringing on existing patents
• Ensuring proper blast protection for instrument and control components
• Carefully managing the structural geometry constraints of double-tier configurations
As industrial facilities continue to prioritize personnel safety and equipment availability, arc-resistant switchgear will remain a growing segment of the North American MV market — driving continued innovation in pressure management and enclosure engineering.
Related topics: Medium-voltage switchgear specifications | IEEE C37.20.2 | NEMA enclosure ratings | arc flash hazard analysis (IEEE 1584) | motor control center design
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.