New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
Electric Vehicles Charing Infrastructure
Features
• Eaton’s Bussmann® series High-speed fuse links have leading DC performance which makes them theideal choice for the protection of high-power DC Charging station applications.
• Higher voltage rating provides overall system efficiency using smaller, more economical conductorswhile meeting the needs of higher voltage system application.
• Higher interrupting rating protects high capacity system needed for both AC and DC side.
• Wide range of solutions available for the protection of AC Input lines, Auxiliary circuits, DC Conditioningcircuits and High Voltage DC/DC Converters for up to 400kW+ rated chargers.
• Demonstrated performance in extreme temperature cycling conditions ensure your installation will beprotected by the best possible and most suitable circuit protection solutions.
• Low watts loss and cool running extend the longevity of the components.
• Team of Electrical Engineering experts on hand to help find the correct circuit protection solutions for yourapplications order.
Storage
• Fuses shall be stored in a dry warehouse or shelf, keep away from water.
• The storage temperature of the product is - 40OC ~ 85OC, the relative humidity is less than 95%, andthere is no condensation. In addition, they must be stored in a non corrosive environment.
• Any fuse submerged in water or sprayed can no longer be used, and any fuse exposed to fire or otherforms of overheating can no longer be used.
Transportation
• During transportation, it shall be rainproof, moisture-proof to avoid severe ground vibration and impact.
Temperature Altitude
• Normal condition -5OC ~ 40OC
• Allowed condition (Derating) -40OC ~ 125OC
• During the rated current test of the fuse, it shall be separately installed in the natural air without ventilation, and there shall be no other heating parts or heat dissipation parts within 1m except the connectingwires. When the fuse operates above 20o C , the rated current needs additional correction.
• Allowed condition (Derating) 2000-5000m
• Parameter correction of altitude change: higher altitude mainly leads to insulation deterioration, heat dissipation condition deterioration and air pressure change.
DC charging station application
C10G Series
C10GXX-C/-TL/-BL/-1P/-PCB
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system.
Basic data
• Voltage rating: 250Vac-500Vac
• Current rating: 10A-50A
• Interrupting rating: 2.5kA/250Vac,3.9kA/400Vac,1.5kA/500Vac
• Standards follow: UL248-14
C10G Series
C14L38G85-PCB
C14L38G85-PCB
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system.
Basic data
• Voltage rating: 500Vdc
• Current rating: 85A
• Breaking capacity: 20kA
• Standards follow: UL248-13
Technical data
C14L38G85-PCB
Dimension (mm):
10D32L63-PCB
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system.
Basic data
• Voltage rating: 250Vac,500Vac,420Vdc
• Current rating: 63A
• Interrupting rating: 10kA/250Vac,2.0kA/500Vac,2.0kA/420Vdc
Technical data
GBH Series
GBH(-V)-XXX
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system.
Basic data
• Voltage rating: 500Vac (Consult Bussmann for DC ratings)
• Current rating: 10A-30A • Interrupting Rating: 5kA at ≥ 20% pf
FWE Series
Description
Eaton’s Bussmann series 1000 V d.c. FWE High speed fuses, specifically designed for EV Charging stations,now available in multiple fuse body sizes.
Basic data
• Fuse body sizes:
• Cylindrical 10 x 38 mm /
• Cylindrical 14 x 51 mm /
• North American round body fuse
• Rated voltage 1000 V d.c. (IEC/UL)
• 50 kA breaking capacity tested
• 10 mS time constant tested (suitable for most DC applications)
• Operating class: aR
• Standards / Agency information: IEC 60269-4 / UL 248-13 recognised / CE
Technical data
FWE Series
CBX000S Series
CBX000S-800(-IN)
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system up to800Vdc.
Basic data
• Voltage rating: 800Vdc • Current rating: 25A-400A • Classification: aR
• Standards follow: IEC60269-4 / GB13539.4
• Interrupting rating: 50kA DC (1ms tc, 800Vdc)
Technical data
XXXCBX000S-800
Dimension (mm):
XXXCBX000S-800-IN
Dimension (mm):
CBX000S Series
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system up to1000Vdc.
Basic data
• Voltage rating: 1000Vdc • Current rating: 25A-250A
• Classification: aR • Standards follow: IEC60269-4 / GB13539.4
• Interrupting rating: 50kA DC (1ms tc, 1000Vdc)
CBX01S Series
CBX01S-1000(N)
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system up to1000Vdc.
Basic data
• Voltage rating: 1000Vdc
• Current rating: 32A-400A
• Classification: aR
• Standards follow: UL248• Interrupting rating: 50kA
CBXS-1000-0 Series
100CBXS-1000-0/-TI/-T2
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system up to1000Vdc.
Basic data
• Voltage rating: 1000Vdc
• Current rating: 100A
• Classification: aR
• Standards follow: GB13539.4 / CCC / TUV
• Interrupting rating: Max 50kA
CBXS-1000-0 Series
100CBXS-1000-T2
Dimension (mm):
CBXS-1000-0 Series
200CBXS-1000-0/-T1/-T2
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system up to1000Vdc.
Basic data
• Voltage rating: 1000Vdc
• Current rating: 200A
• Classification: aR
• Standards / Agency information: GB13539.4 / CCC / TUV
• Interrupting rating: Max 50kA
CBXS-1000-0 Series
400CBXS-1000-0
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system up to1000Vdc.
Basic data
• Voltage rating: 1000Vdc
• Current rating: 400A
• Classification: aR
• Standards / Agency information: IEC 60269-4 / CCC / CE
CBXS-1000-0 Series
800CBXS-1000-0
Description
These fuse links are capable of interrupting extremely high fault currents provided by electrical system up to1000Vdc.
Basic data
• Voltage rating: 1000Vdc
• Current rating: 800A
• Classification: aR
• Standards / Agency information: IEC 60269-4 / CCC / CE
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.