New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.
In 10kV substations, vacuum circuit breakers are commonly adopted for both incoming lines and transformer high-voltage sides. Standard rated currents include 630A, 1250A, 1600A, 2000A, 2500A, 3150A, and 4000A, paired with corresponding breaking capacities as follows:
630A: 20–25kA
1250A & 1600A: 31.5kA
2500A & 3150A: 40kA
For user substations and industrial loads in Beijing, a 20–25kA breaking current suffices. For power utilities and generation facilities, circuit breakers should be rated for 31.5–40kA.
Given current power distribution transformer capacities not exceeding 2500kVA, the high-voltage current can be calculated as:
Single transformer: Ig = 1.05 × Se / (√3 × Ue) ≈ 152A
Dual transformers (1.3×): Ig ≈ 187A
Thus:
If only one transformer feeder exists: use 630A breaker.
If there are multiple feeders or standby lines: opt for 1250A or 1600A.
With 10kV short-circuit currents in Beijing not exceeding 25kA, a 25kA breaker is typically sufficient.
According to GB13539.1-2002 / IEC60269-1:1998, standard rated fuse currents range from 0.5A to 1250A.
If a load-break switch is used on the 10kV side, a combined load-break switch and fuse protection scheme is employed. Fuse rating (Irr) is calculated using:
Irr = K × Igmax
Where:
Igmax = 1.1 × rated current
K = 1.1–1.3 (without motor starting), 1.5–2.0 (with motor starting), typically ~1.5
Example:
For an 800kVA transformer:
Ig = 46.2A → Irr = 1.1 × 1.5 × 46.2 = 76.23A
→ Fuse rating = 80A
For metering: Rated fuse current = 0.5A
For protection and measurement: Rated fuse current = 1A
These values ensure precise fault detection and secure operation under minimal burden conditions.
Rated Voltage:
According to GB/T 50064-2014, surge protection must accommodate:
Temporary overvoltages (TOVs)
Switching surges
Lightning-induced surges
Given Um = 12kV for 10kV systems:
Low resistance grounded systems: MOA rated voltage ≥ 12kV
Arc-suppression coil grounded: MOA rated voltage ≥ 15kV
Continuous operating voltage (Uc):
Low-resistance: ≥ 9.6kV
Arc-suppressed: ≥ 12kV
Discharge Current:
Distribution equipment: 5kA
Motors: 2.5kA
Transformers/neutral points: 1.5kA
Residual Voltage:
Using the formula:
Ul.p ≤ Ue.l.i / K16, with K16 = 1.25
Arc-suppression coil grounded: Ul.p ≤ 60kV
Low resistance grounded: Ul.p ≤ 48kV
Selection Example:
HY5WZ(S)-17/45, where:
HY: Composite zinc oxide arrester
5: 5kA discharge current
W: Gapless
Z: Substation type
S: Distribution type
17: Rated voltage (kV)
45: Residual voltage (kV)
Installation:
With shared PT: installed in PT cabinet
Without PT: placed on transformer feeder panel
The sectional breaker should match the incoming line breaker in rated parameters, including CTs. The instantaneous and time-delay trip settings should lie between the upstream breaker and the downstream load's maximum fault current.
In Beijing’s power grid, both 10kV and 0.4kV buses often operate in split configuration to limit short-circuit currents. Sectional switches must support 3-out-of-2 interlocking (closed-loop protection).
Primary ratings: 15A–4000A
Secondary ratings: 5A or 1A
Accuracy:
Metering: 0.2S or 0.5S
Protection: 10P10 or 10P15
Metering CT Selection Formula:
N = Ie / (0.7 × 5)
Where Ie = primary rated current
Example CT Ratios:
Transformer Capacity | Ie (A) | CT Ratio (A) |
---|---|---|
400kVA | 23 | 40/5 |
800kVA | 46.2 | 75/5 |
1600kVA | 92.4 | 150/5 |
Protection CT Selection:
Ensure CT saturation current ≥ 1.3 × maximum short-circuit current.
Thermal & Dynamic Stability:
Thermal: CT must endure 25kA for 4s (10kV)
Dynamic: Idyn ≥ 2.55 × 25kA = 63.75kA
Zero-Sequence CTs:
Typical ratios: 50/5, 75/5, 100/5, 20/1
Systems with grounding via arc suppression coil: protection acts at ≥5A
Choose low-ratio CTs for sensitivity; e.g., 100/5 gives 0.25A secondary at 5A primary
Based on DL5222-2005, for copper conductors at 25°C and 4s fault duration:
Fault Current | Required Area (mm²) |
---|---|
25kA | 257.5 |
31.5kA | 324.4 |
40kA | 412 |
63kA | 648.9 |
80kA | 824 |
A. Voltage Level:
Based on GB 50217-2007:
Low-resistance grounding (≤1 min fault): ≥6.5kV
Arc-suppressed coil grounding (<8h): ≥8.7kV
Ungrounded (>8h): ≥11kV
B. Conductor Sizing:
1. Load Carrying Capacity:
Use:
Ig = K × Se / (√3 × 10)
Where K ≈ 1.3 for overloading margin
Adjust for temperature, soil resistance, and installation factors (K1, K2, K3).
2. Thermal Stability Check:
S ≥ 100 × √Q / C, where
Q = Id² × t
t = 0.245s
C (for XLPE Cu cable) = 13279
Example:
For 25kA fault, S ≥ 93.2mm²
→ Use 150mm² XLPE cable for external feeders
For Transformer Feeder Cables:
Cables only need to meet continuous current demand—thermal performance is inherently satisfied due to lower fault levels on the HV side.
Designing a 10kV distribution system requires rigorous component selection rooted in electrical standards, fault tolerance, and system coordination. From vacuum breakers to surge arresters, each element must be carefully sized not only for nominal operation but also for extreme contingencies. Engineering foresight in this regard is essential to ensure reliability, safety, and long-term operational integrity.
New industry Technology regarding to Bussmann fuse, ABB breakers, Amphenol connectors, HPS transformers, etc.