The Eaton precision air conditioning unit is available in 9 capacities covering 27.6 to 103.6 kW of total cooling. Units are supplied with under-floor or top-discharge air paths, and the table lists total and sensible cooling, airflow, fan and compressor data for each model.
| Technical data | |||||||||
| Model | SAC1DA27 | SAC1DA36 | SAC2DA41 | SAC1DA47 | SAC2DA52 | SAC1DA53 | SAC2DA63 | SAC2DA84 | SAC2DA103 |
| Total Cooling Capacity (kW) | 27.6 | 36.4 | 41.3 | 47.4 | 52.2 | 53.3 | 63 | 83.7 | 103.6 |
| Sensible Cooling Capacity (kW) | 24.8 | 31.5 | 41.3 | 44.3 | 46.3 | 49 | 58.3 | 74.1 | 88.6 |
| Airflow (m³/h) | 7,300 | 8,800 | 12,500 | 13,500 | 15,400 | 15,000 | 17,600 | 20,500 | 24,300 |
| Fan Quantity | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 3 | 3 |
| Fan Power (kW) | 2.1 | 2.3 | 3.2 | 3.6 | 4.5 | 4.3 | 4.6 | 5.5 | 7.1 |
| Compressor Quantity | 1 | 1 | 2 | 1 | 2 | 1 | 2 | 2 | 2 |
| Compressor Power (kW) | 5.5 | 7.2 | 8.4 | 9.3 | 11 | 11.2 | 12.4 | 16.4 | 22.2 |
| Humidification (kg/h) | 5 | 8 | 8 | 8 | 8 | 8 | 8 | 15 | 15 |
| Electric Heating Capacity (kW) | 6 | 9 | 9 | 9 | 9 | 9 | 12 | 18 | 18 |
| Weight (kg) | 403 | 488 | 596 | 572 | 629 | 572 | 725 | 850 | 853 |
| Unit Dimensions W × D × H (mm) | 1000x890x1980 | 1400x890x1980 | 1750x890x1980 | 2150x890x1980 | 2550x890x1980 | ||||
| Model | ASVA21-036 | ASVA21-045 | ASVA21-032 | ASVA31-058 | ASVA21-036 | ASVA41-076 | ASVA21-045 | ASVA31-058 | |
| Condenser Quantity | 1 | 1 | 2 | 1 | 2 | 1 | 2 | 2 | 2 |
| SAC*U*** | SAC1UA27 | SAC1UA36 | SAC2UA41 | SAC1UA47 | SAC2UA52 | SAC1UA53 | SAC2UA63 | SAC2UA84 | |
| Total Cooling Capacity (kW) | 27.6 | 36.4 | 41.3 | 47.4 | 52.1 | 53.3 | 62.9 | 84 | 103.7 |
| Sensible Cooling Capacity (kW) | 24.8 | 31.5 | 41.3 | 44.3 | 45.6 | 49 | 57.8 | 75.5 | 88.1 |
| Airflow (m³/h) | 7,300 | 8,500 | 12,500 | 13,500 | 14,900 | 15,000 | 17,300 | 21,200 | 24,000 |
| Fan Quantity | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 3 | 3 |
| Fan Power (kW) | 2.3 | 2.5 | 3.2 | 3.9 | 4.3 | 4.5 | 4.5 | 6.2 | 7.2 |
| Compressor Quantity | 1 | 1 | 2 | 1 | 2 | 1 | 2 | 2 | 2 |
| Compressor Power (kW) | 5.5 | 7.2 | 8.4 | 9.3 | 11 | 11.2 | 12.4 | 16.4 | 22.2 |
| Humidification (kg/h) | 5 | 8 | 8 | 8 | 8 | 8 | 8 | 15 | 15 |
| Electric Heating Capacity (kW) | 6 | 9 | 9 | 9 | 9 | 9 | 12 | 18 | 18 |
| Weight (kg) | 394 | 488 | 596 | 545 | 602 | 545 | 705 | 813 | 820 |
| Unit Dimensions W × D × H (mm) | 1000x890x1980 | 1400x890x1980 | 1750x890x1980 | 2150x890x1980 | 2550x890x1980 | ||||
| Model | ASVA21-036 | ASVA21-045 | ASVA21-032 | ASVA31-058 | ASVA21-036 | ASVA41-076 | ASVA21-045 | ASVA31-058 | |
| Condenser Quantity | 1 | 1 | 2 | 1 | 2 | 1 | 2 | 2 | 2 |
DC fuse, EV fuse, high speed fuse, current limiting fuse cross reference.
Bussmann, Littelfuse, Mersen, ABB, Schneider, Eaton, HPS( Hammond Power Solutions), Amphenol, Molex distributor.
NH fuses are knife-blade fuse links used in matching industrial bases and switchgear. This guide exp.....
MOREEaton Bussmann 1000VDC 400A,high speed breaker...
MOREEnergy Storage System Electrical Protection Solution, Fuse,Pyrofuse, Breaker, Bussmann, Eaton, Litte.....
MORENH fuses are knife-blade fuse links used in matching industrial bases and switchgear. This guide exp.....
MOREEnergy Storage System Electrical Protection Solution, Fuse,Pyrofuse, Breaker, Bussmann, Eaton, Litte.....
MOREBussmann fuse catalog, EV fuse,DIN type fuse, type.....
MORE